1 NO contact potential free 10A/250V AC.
Only 0.8 watt standby loss. Encrypted
wireless, bidirectional wireless and
repeater function are switchable.
For installation.
45mm long, 45mm wide, 33mm deep.
Supply voltage 230V.
If a power failure occurs, the switching
state is retained. If a power failure occurs
repeatedly, the device is switched off in a
defined sequence.
After installation, wait for short automatic
synchronisation before the switched
consumer is connected to the mains.
This heating/cooling relay evaluates the
information from wireless temperature
controllers or sensors. Possibly supple-
mented by window/door contacts, motion
detector, Hoppe window handles and
wireless pushbuttons.
Starting in production week 11/14, you
can teach in encrypted sensors. You
can switch on bidirectional wireless
and/or a repeater function.
Every change in state of the contact is
confirmed by a wireless telegram. This
wireless telegram can be taught-in into
other actuators and the GFVS software.
Especially into a FSR61 to synchronously
switch a heat circulating pump with the
valves.
GB
Only skilled electricians may install
this electrical equipment otherwise
there is the risk of fire or electric
shock!
Temperature at mounting location:
-20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity:
annual average value <75%.
Wireless actuator
Heating/cooling relay
FHK61U-230V
30 100 050 - 2
valid for devices from production week
11/14 (see bottom side of housing)
Function rotary switches
Top rotary switch for operating modes:
H1: Heating operation with PWM control
at T = 4 minutes. (suitable for valves
with thermoelectric valve drive)
H2: Heating operation with PWM control
at T = 15 minutes. (suitable for valves
with motor-driven valve drive)
H3: Heating operation with 2-point
control.
K1: Cooling operation with PWM control
at T = 15 minutes.
K2: Cooling mode with 2-point control.
Switchover is visualised by LEDs flashing.
Bottom rotary switch for adjustable
hysteresis and PWM influence:
Left stop: lowest hysteresis 0.5°.
Middle position: hysteresis 2.5°.
Right stop: largest hysteresis 4.5°.
Inbetween, divisions in steps of 0.5°
visualised by LEDs flashing.
Two-point control mode:
The hysteresis rotary switch sets the
required difference between the switch-on
and switch-off temperatures.
When the 'actual temperature >= reference
temperature', the device is switched off.
When the 'actual temperature <=
(reference temperature - hysteresis)', the
device is switched on. The signs are the
opposite in cooling mode.
PWM control mode:
The hysteresis rotary switch set the required
temperature difference at which the device
is switched on at 100%. When the 'actual
temperature >= reference temperature',
the device is switched off.
When the 'actual temperature <=
(reference temperature - hysteresis)', the
device is switched on at 100%.
If the 'actual temperature' lies between the
'reference temperature - hysteresis' and
the 'reference temperature', the device is
switched on and off with a PWM in steps
of 10% depending on the temperature
difference.
The lower the temperature difference, the
shorter the switch-on time. As a result of
the settability of the 100% value, the
PWM can be adapted to the heater size
and inertia. The signs are the opposite in
cooling mode.
In heating mode, the frost protection
function is always enabled. As soon as
the actual temperature drops below 8°C,
the temperature is controlled in the
selected operating mode to 8°C.
If one or several windows are open, the
output remains off provided the window/
door contacts FTK or Hoppe handles
are taught-in. In heating mode, however,
the frost protection remains enabled.
As long as all taught-in motion detectors
FBH detect no motion, the device is
switched to setback mode. In heating
mode, the reference temperature is set
back by 2°; in cooling mode, it is raised
by 2°. As soon as a motion detector
signals movement again, the device is
switched to normal mode.
When a wireless pushbutton is taught-in,
the assignment of the 4 keys is assigned
with the following fixed functions: Top
right: Normal mode (can also be enabled
by timer). Bottom right: Night setback
mode by 4°; in cooling mode, raised by
4° (can also be enabled by timer). Top
left: Setback mode by 2°, in cooling mode,
raised by 2°. Bottom left: Off (in heating
mode, frost protection enabled; in cooling
mode permanent off). If the motion
detector and wireless pushbutton are
taught-in at the same time, the last tele -
gram received is always the one that is
valid. A motion detector therefore switches
off a setback mode selected by wireless
pushbutton when a movement is detected.
Malfunction mode:
If a temperature sensor fails to receive a
wireless telegram for longer than 1 hour,
the LED lights up and the device switches
to fault mode. In heating mode, the device
remains switched on for 1.2 minutes at H1
and switched off for 2.8 minutes. When
set to H2 and H3 the 'ON' time is 4.5
minutes and 'OFF' time is 10.5 minutes.
The device is switched off in cooling
minutes
and
OFF
time
is 10
.
5
minutes
.
The device is switched off in cooling
mode. When a wireless telegram is
again received, the LED goes out and the
device switches back to normal mode.
The LED performs during the teach-in
process according to the operation
manual. It shows wireless control
commands by short flickering during
operation.
Typical connection
Technical data
Rated switching capacity 10A/250V AC
Standby loss (active power) 0.8W
Teaching-in wireless sensors in wire
-
less actuators
All sensors must be taught-in in
actuators so that they can detect and
executetheir commands.
Teaching-in actuator FHK
61U-230V
The teach-in memory is empty on
delivery from the factory. To ensure that
a device was not previously taught-in,
clear the memory completely:
Turn the upper rotary switch to CLR.
The LED flashes at a high rate. Within
10 seconds, turn the lower rotary switch
three times to right stop (turn clockwise)
and back again. The LED stops flashing
and goes out after 2 seconds. All taught-
in sensors are cleared; the repeater and
the confirmation telegrams are switched
off.
Termékspecifikációk
| Márka: | Eltako |
| Kategória: | nincs kategorizálva |
| Modell: | FHK61U-230V |
Szüksége van segítségre?
Ha segítségre van szüksége Eltako FHK61U-230V, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók nincs kategorizálva Eltako
29 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
28 Augusztus 2024
Útmutatók nincs kategorizálva
- nincs kategorizálva VAIS
- nincs kategorizálva SmallRig
- nincs kategorizálva PATLITE
- nincs kategorizálva Steelbody
- nincs kategorizálva Nethix
- nincs kategorizálva Grosfillex
- nincs kategorizálva EarFun
- nincs kategorizálva TAURUS Titanium
- nincs kategorizálva Honor
- nincs kategorizálva Studio Titan
- nincs kategorizálva Red Panda
- nincs kategorizálva Blebox
- nincs kategorizálva Nûby
- nincs kategorizálva The Grainfather
- nincs kategorizálva Alcon
Legújabb útmutatók nincs kategorizálva
10 Április 2025
10 Április 2025
10 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025