NETWORK ANALYZER
MPR-53CS 
General
MPR-53CS measures all the electrical parameters that belong to network. MPR-
53CS is designed for protection of electrical system. Measured parameters are 
shown in 5 separate displays. This allows to monitor more than 50 parameters at the 
same time. MPR-53CS has also MODBUS serial interface feature. 
The table below shows the parameters that are measured by MPR-53CS:
Functions of Buttons
Used for switching between (VLN, VLL, A, W, VAr, VA, Cos   , kWh, 
kVarh, THD, C-1, C-2, tot-h, run-h) parameters in the monitoring 
mode. 
Used for switching between previous ( ) or next ( ) menu in main 
menu or submenus and also use for changing chosen values. 
(SET) Used for switching between min., max demand and instant 
values in the monitoring mode. In display when run hour (run -h) is 
displayed, if SET button is pressed, it shows setpoint hours 
(SP -h) counted time. In latch function when button feature is used, 
with SET button latch position operation is done. Switching to the 
programming mode if it pressed for 3 sec. It is used for switching to the 
menu and saving changes for the parameters in programming mode. 
(Back) Used for switching between SW, SVA and Hz parameters in the 
monitoring mode. Used for switching previous digit in submenu.
(ESC) Used for switching between SVAr and Cos
  values in the 
monitoring mode. Used for entering to upper menu or it is used to quit 
from the programming mode without saving values in the programming 
mode. 
When Pin is activated, after pressed “SET” button for 3 seconds, PIN is 
required; after entering correct PIN code, you can enter to menu. 
Use of MPR-53CS:
By using Up/Down buttons parameters are shown in L1, L2, L3 displays (VLN; VLL; 
A; IN; W; VAr; VA; Cosj; kWh, kVarh, THD, C-1, C-2, tot-h, run-h). Total Active (SW), 
Total Apparent Power (SVA) and Frequency (Hz) are selected by Back button.
Total Reactive Power (SVAr) and Cos   are selected by Esc button. 
Digital Inputs
MPR-53CS has 2 digital inputs. Digital inputs have 2 functions :   
- If remote control is activated (battery, thermostat, circuit breaker, engines status) 
the status of devices connected to digital input will be seen according to datas in 
time regiters. 
- When digital inputs of energy count, run hour and latch menus are selected, digital 
inputs controls these menu’s functions (Example: It is used for measuring of energy
separately at the using of network and generator). 
aren’t any signal in digital inputs. Otherwise “on”. 
Energy Pulse Outputs
MPR-53CS has 2 energy pulse outputs. Pulse outputs give the pulses only for 
E-1 (energy counter). Pulse outputs can be programmed one by one. When pulse 
outputs give pulse “P1” (Pulse 1) and “P2” (Pulse 2) lights (Not included in the PK-26 
Pul1 ve Pul2 : There are sub menus o-1 (pulse 1) and o-2 (pulse 2) in pulse out 
menu. Device gives pulse according to chosen energy parameters [Active energy 
(ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)]. For energy count values, look at 
the pulse menu.
Pulse Counter
MPR-53CS has 2 pulse counters (C-1, C-2). C-1 counts the pulses from digital input 
1 and C-2 counts the pulses from digital input 2. 
Pulse counter detect the pulses which are in condition of signal 1. When the number 
of pulses reach “pulse C1/2 ratio” value, releated pulse counter is increase by 1. 
When C-1/C-2 counters are not activated in pulse counter menu, instant values of 
C-1/C-2 are not displayed.
Note: DC signals must be use supplied in order to use this menu. 
Digital Outputs 
MPR-53CS has 6 digital outputs. Only 2 of them have LED on the front panel. These 
are “O-3” and “O-4” LEDs (“O-4” light is not available in the PK-26 box).
When digital outputs are activated, related addresses can be displayed with “xxx” 
values, only “O-3” and “O-4” LEDs are lighted for digital outputs 1 and 2 on front 
panel. Digital output on devices menu’s output parameters;  1/2/3/4/5/6 correspond 
to “3/4/5/6/7/8” parameters. 
User can check the digital output register for fault about set parameters by 
communicating with the device. 
Relay Outputs 
MPR-53CS has 2 NO contact outputs. On front panel, MPR-53CS has 
o-1 and o-2 LEDs. When alarm parameters are selected 1 (out 1) and 2 
(out 2) for output, device gives alarm. Related contact outputs will close and LEDs 
will be on. 
Total Hours
Shows running time of MPR-53CS from the beginning. User can not reset this 
counter.
Run Hours
Shows MPR-53CS’s running hour. This can be resetted and can be controlled by 
it runs if there is a signal in digital inputs. It does not run if there is no signal in digital 
inputs.
Setpoint Hours
By pressing SET button during monitoring of Run Hour, set point hour can be 
monitored. Setpoint hour runs according to run hour. When run hour runs actively, 
setpoint hour runs. When set time value reaches to “hoU r SP” which set by user, 
selected output will be active (1) and give an alarm and setpoint hour continues to 
count. This alarm can be erased by resetting setpoint hour or getting out from locked 
position. When setpoint output is required to remove by using latch function, “latch 
auto” function can’t be used. If MPR-53CS returned to normal operation from failure 
by using latch function, it automatically starts the time from zero. To make setpoint 
hour passive, the value of SP hour is set “0000”. This setting only closes the setpoint 
Note: Total hour and run hour do not count during electric interruptions. Total hour 
measurement mode, by scrolling UP and DOWN buttons, user can see running 
time. Run hour display is shown is “HH HHH H.HH” (H=Hour) form. All the values 
shown on the display are in terms of hour. For example, if displayed value is 00 000 
1.75, means that device worked for 1.75 hours. If the user wants to convert last digit 
to minutes, last digitx0.6 (75x0.6=45 minutes) formula is used conversion. Device 
worked 1 hour 45 minutes. 
İmportant: In “hoU r SP” menu when chosen output is activated and devices is set 
for giving an alarm at the end of one hour. After counting to 99 on display, devices 
gives an alarm (1 hour = 60 min. for MPR-53CS on display “99” corresponds to “59”). 
Monitoring of Min.- Max. and Max. Demand Values:
LN, VLL, A, W, VAr, VA,  W,  VAr,  VA; 
W,  VA,  VAr.
If measured instant value is smaller than min. value, they are saved as new min. and 
if measured instant value is bigger than instant max. value, new max. value is saved. 
During demand time (example 15 min.) demand value is got max. demand.
If press SET button when the device is in any parameter (example “A”) min., max. 
parameter (example “Cos  ”) is displayed, the device continues to display instant 
parameters.
Monitoring THD Values
If “VLN” and “THD” LED’s light on together, voltage “THD” is monitored. And if “A” 
and “THD” LEDs light on, current “THD” is monitored. 
Monitoring Neutral Current
When instant current values of 3 phases are shown on the display, by pressing the 
“DOWN” button, I-n (neutral current) is displayed. “A” LED continues light on. When 
connection form is chosen as delta, this display will be closed.
Monitoring Setpoint Parameters Fault Warning
Device activates the selected output if there is a failure because of any causes. 
User can set more then one parameters to output, so outputs can be monitored 
depending which parameter and this parameters protection type (low, high, both of 
them) even in failure situation when “rUn -h” menu is displayed, pushing “DOWN” 
button or when VLN is displayed pushing “UP” button, failure parameter  will be seen 
as “SP -xx h/L/hL x-x x-x”. If there is a no failure, you will not see such a display. 
After pressing SET button you can see other failure parameter. 
Calculation Methods for Active / Reactive Values
If the dot on the right down corner blinks it shows that active power and reactive 
powers directions are negative. There are 2 methods for calculating total active and 
total reactive powers.
1) Active and reactive powers are calculated by summing import and export values 
and shown as a single value. 
2) Active and reactive powers are calculated one by one according to import/export 
condition.
Note :
1) 
During  W LED is displayed, if the dot at the most right down digit of the forth 
display lights on, it represents that displayed value is export active power value. 
If not, it represents that displayed value is import active power value.
2) During 
display lights on, it represents that displayed value is capacitive reactive power 
value. If not, it represents that displayed value is inductive reactive power value. 
stand by.
1
Termékspecifikációk
| Márka: | Entes | 
| Kategória: | nincs kategorizálva | 
| Modell: | MPR-53CS-96 | 
Szüksége van segítségre?
Ha segítségre van szüksége Entes MPR-53CS-96, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók nincs kategorizálva Entes
                        
                         4 Január 2025
                        
                    
                                                            
                        
                         4 Január 2025
                        
                    
                                                            
                        
                         28 December 2024
                        
                    
                                                            
                        
                         5 Szeptember 2024
                        
                    
                                                            
                        
                         4 Szeptember 2024
                        
                    
                                                            
                        
                         4 Szeptember 2024
                        
                    
                                                            
                        
                         4 Szeptember 2024
                        
                    
                                                            
                        
                         4 Szeptember 2024
                        
                    
                                                            
                        
                         4 Szeptember 2024
                        
                    
                                                            
                        
                         4 Szeptember 2024
                        
                    
                                                            Útmutatók nincs kategorizálva
- nincs kategorizálva Albert Heijn
- nincs kategorizálva Hamax
- nincs kategorizálva Bernina
- nincs kategorizálva Celly
- nincs kategorizálva Lian Li
- nincs kategorizálva Antari
- nincs kategorizálva Miomare
- nincs kategorizálva Drive Medical
- nincs kategorizálva Procare
- nincs kategorizálva Sennheiser
- nincs kategorizálva Michigan
- nincs kategorizálva Martha Stewart
- nincs kategorizálva A4 Tech
- nincs kategorizálva Strex
- nincs kategorizálva Axis
Legújabb útmutatók nincs kategorizálva
                        
                         10 Április 2025
                        
                    
                                                            
                        
                         10 Április 2025
                        
                    
                                                            
                        
                         10 Április 2025
                        
                    
                                                            
                        
                         9 Április 2025
                        
                    
                                                            
                        
                         9 Április 2025
                        
                    
                                                            
                        
                         9 Április 2025
                        
                    
                                                            
                        
                         9 Április 2025
                        
                    
                                                            
                        
                         9 Április 2025
                        
                    
                                                            
                        
                         9 Április 2025
                        
                    
                                                            
                        
                         9 Április 2025