Használati útmutató Eberle Easy 3 sw
Eberle Termosztát Easy 3 sw
Olvassa el alább 📖 a magyar nyelvű használati útmutatót Eberle Easy 3 sw (3 oldal) a Termosztát kategóriában. Ezt az útmutatót 19 ember találta hasznosnak és 6 felhasználó értékelte átlagosan 4.3 csillagra
Oldal 1/3

1. Applications
The easy 3s electronic clock thermostat is designed for room
temperature control in conjunction with:
•heating systems, e.g. hot-water heaters, convector heaters
or oor heating
• electricconvectorheaters,ceilingandstorageheating
• night-storageheaters
• chillers
• circulationpumps
• burnersandboilers
• heatpumps,etc.
• airconditioningapplications(coolingonly)
Features
• verysimpleoperation
• comfortandsetbacktemperatureadjustable
• 5operatingmodes(byrotaryswitch)for:
permanentcomforttemperature(5…30°C)
permanentsetbacktemperature(5…30°C)
clockmode(automatic)
frostprotection(5°Cxed)
OFF
• Indicator lamps for: heat demand
setbackmode
• availablewithdailyorweeklytimer
• controlbyphoneremoteswitchpossible
•outputsignal PWMor ON/OFF regulation(adjustable via
jumper)
• relayoutput,1xchangeovercontact
• remote sensor optional
• emergency operation at sensor failure
• hingedcover
• newdesign2000
2. Function description
The clock thermostat is designed to control the room tem-
perature.
In the automatic mode, a changeover is eected between
comfortandsetbackmodebythebuiltintimer.
Optionally remote sensor can be used instead of built-in
sensor.
Insetbackmodethegreenindicatorlamplightsup.
Ifroomtemperaturedropsbelowsetvalue,heatingwillstart,
theredindicatorlampwilllightup.
Indicator lamps
Red indicateswhencontrollerdemandsheat,
Green indicateswhensetbackmodeisactivated.
Red ashingforfailure.Operatingvoltagetobeswit-
chedOFFandONagain.
Controller heat demand at PWM
Ifroomtemperaturedropsbelowthesetvalue,heatingmode
will start.The controller outputis in the formof pulsesof
varyinglength (PWM).The lengthof the pulses dependson
thedierencebetweensetandactualroomtemperature.
The sum of pulseand pause times can be selected with J4
(between10or25min.).
If therearelargetemperature dierences, the controller will
switch ONor OFF permanent, e.g.when changing overto
temperature setback mode. PWM should onlybe used for
current≤10A
On
Off
Temperature
10/25 min
set temperature
Fig.1:Characteristic of impulse pause ratio depending on
temperature
Cycle time setting
Forinert applications (e.g.burners) werecommend the long
cycletime.
Forquickapplications (e.g.electricdirectheaters)we recom-
mendtheshortcycletime.
Plug-in jumper J4
(rightsideofboard)
Time
Double-polejumper
connection
25 min
(as-deliveredcondition)
Single-polejumper
connection
10min
Heat demand of the controller at ON/OFF regulation
When roomtemperature dropsbelow set temperaturethe
output willbe switched on,whereas it willbe switched o,
whensetvalueisexceeded.
set temperaturetemperature
OFF
ON
Hysteresis
Fig.2:ON/OFFregulation
Plug-in jumper J3
(rightsideofboard)
Regulation
Double-polejumper
connection
ON/OFF
Single-polejumper
connection
PWM (asdeliveredcondition)
Phone remote switch (onlyavailableatspecialvariants)
Viaan external phone switching device the conroller can be
put into modeof comfortor setback temperature. As long
as contact (terminal19) is closed, the comfort temperature
will be “used“. This functionistactivatedin themodes2
automatic, setbacktemperaturepermanentandÑ P
Frostprotection.
3. Installation
Thecontrollershouldbearrangedinaplacewithintheroom
which:
• iseasilyaccessibleforoperation
• isfreefromcurtains,cupboards,shelves,etc.
• enablesfreeaircirculation
• isfreefromdirectsunradiation
• isfreefromdraughts(e.g.openingofwindowsanddoors)
• isnotaecteddirectlybythesourceofheat
• isnotlocatedonanexternalwall
• islocatedapprox.1,5maboveoorlevel
MountingdirectlyonconduitboxorwithadapterframeARA
easy.
Electric connection
Warning!Disconnectelectriccircuitfromsupply.
Proceed as follows:
• pullotemperaturesettingknob
• pushretaininghookoutwardsusingscrewdriver
• removehousingcover
•make connection in compliance with wiring diagram
(seehousingcover).
• watchnotes
Remote sensor
Having connectedtheremote sensor, the integralsensing
componentwillbeswitchedoautomatically.
The sensor cableis extendableup to a lengthof max.50m.
Please use a two-core 230V cablewith a cross section of 1.5
mm.
Thesensorcable(F193720)shouldbeinstalledintoaprotecti-
ontube(pocket).Thisfacilitateslaterreplacement.
Incaseoffailure(breakorshort-circuit)thecontrollerswitches
into emergency operation:
atPWM: 30%heatingcapacitiy
at ON/OFF: Relay OFF
Warning! Sensor cables carry operating voltage.
4. Technical data
Temperature setting range:
comfort temperature
setback temperature
frost protection
5…30°C
5…30°C
approx. 5°C xed
Regulationproportional controller
(due to PWM quasi-continuous, see Fig.1)
Cycle periodadjustable 10 or 25 min.
(sum of PWM ON and OFF times)
Proportional band1,5K
Hysteresis~0,5K, ≤ 10A see Fig. 2
~0,5K at 16A and use with remote sensor
~2,5K, at 16A without remote sensor
ON/OFF regulationadjustable via jumper
Outputrelay, 1 volt-free* changeover contact
Switching current
Heating
Cooling
10mA…16 A cos = 1ϕ
max. 4 A cos = 0,6ϕ
10mA ...10A cos = 1ϕ
max. 1,5 A cos = 0,6ϕ
Switching voltage24…250V AC
Mode selector switchcomfort / automatic / setback /
frost protection / OFF
Phone remote switch
(as variant)
Input for 230V AC (via an external
phone switching device)
Indicator lamp: red
green
controller demands heat
setback mode
Temperature sensor:internal
Remote sensor
Sensor characteristics
type F190021 (wall mounting)
type F193720 length 4m
both extendable up to 50m
42kΩ at 20°C
26kΩ at 30°C
Range limitationinside setting knob
Clock:
accuracy
switching time setting
power reserve
<10 min./year
every 15 min. with daily timer
every hour with weekly timer
approx. 100 h
Protection class of housingIP 30
Degree of protectionII (see Warning 1)
Ambient temperature0…40°C, without condensation
Storage temperature–25…65°C
Pollution degree 2
Rated impulse voltage4 kV
Ball pressure test
temperature
75 ± 2 °C
Voltage and Current for the
for purposes of interfernce
measurements
230 V, 0,1 A
Dimensions160 x 80 x 36 mm
Weightapprox. 220 g
Energy classIV = 2 %
(acc. EU 811/2013, 812/2013, 813/2013, 814/2013)
* The volt-free contact of this mains-operated unit does
not ensure the requirement for the use of safety ext-
ra-low voltage (SELV).
For units with 230 V supply voltage
Type easy 3st with daily timer
easy 3sw with weekly timer
Article-Nr. easy 3st 517 2701 51 100
easy 3sw 517 2702 51 100
Operating voltage 195…253 V AC 50/60Hz
Power consumption < 1,5 W
For units with low voltage output
Type easy 3st 1mA with daily timer
easy 3sw 1mA with weekly timer
Article No. easy 3st 1mA 517 2711 51 100
easy 3sw 1mA 517 2712 51 100
Operating voltage 195...253V AC 50/60Hz
Switching current >1 mA, >1V or max. 10(4)A AC
Power consumption < 1,5 W
5. Wiring diagram
Symbol explanation
U Heaing PCooling Remote sensor
Phone remote switch
Note
For heating applications
•connectn/cactuatorstoterminal2.
•connectn/oactuatorstoterminal3.
For cooling applications
• connectn/cactuatorstoterminal3
• connectn/oactuatorstoterminal2
• Tousetheredlampasindicatorfor“coolingON”,connectn/o
actuators to terminal 2
• WhenmodeselectorswitchisinOFFposition n/c and n/o
actuatorswillbeclosedlogically.
6. Operation
Temperature setting
1 Comfort temperature (daytimetemperature)
issetbymeansofexternallyvisiblesetingknob(1)
2 Setback temperature (nighttemperature)
issetbymeansofadjustmentknob(2)beneathcover.
Time setting
3 byputtingonengerondial(3)andturninginanydirec-
tion,youcansetthetime.
4 Arrow(4)pointstotheselectedtime.
Switching time setting
5Bringmovable tappets (5)into requiredposition using a
pointedobject.
Outer ring = comfort temperature
Innerring= setbacktemperature
6 Mode selector switch (6)–externally
É Comforttemperature,permanent
2 Automaticmode,time-controlledchangeover
betweencomfortandsetbacktemperature
Ñ Setbacktemperature,permanent
P Frostprotection,permanent(5°C)
OFF,thereisnocontrolactivity.Thecontrolleritselfisnot
disconnectedfromoperatingvoltage.
12
4 563
U46931 01911-088 2
Installation and
Operation Instructions
Electronic
Clock Thermostat
easy 3s
Warning!
Thedevice mayonly be opened and installedaccor-
ding tothe circuitdiagram onthe device orthese
instructions bya qualiedelectrician.Theexisting
safetyregulationsmustbeobserved.
Appropriate installation measures must be taken to
achievetherequirementsofprotectionclassII.
This independently mountableelectronic device is
de-signed for controllingthe temperatureindryand
enclosed roomsonly under normal conditions.The
device conrms to EN 60730, it works according
operatingprinciple1C.
This product shouldnot be disposedof with
householdwaste.
Please recycle the products where facilities for
electronic waste exist. Check with your local
authoritiesforrecyclingadvice.
Termékspecifikációk
| Márka: | Eberle |
| Kategória: | Termosztát |
| Modell: | Easy 3 sw |
Szüksége van segítségre?
Ha segítségre van szüksége Eberle Easy 3 sw, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók Termosztát Eberle
6 Április 2025
4 Április 2025
28 Március 2025
19 Március 2025
16 Március 2025
12 Január 2025
12 Január 2025
2 Október 2024
2 Október 2024
23 Augusztus 2024
Útmutatók Termosztát
Legújabb útmutatók Termosztát
9 Április 2025
7 Április 2025
7 Április 2025
6 Április 2025
6 Április 2025
5 Április 2025
4 Április 2025
3 Április 2025
3 Április 2025
3 Április 2025