1.Product Outlook
DB-9 port 9-pin port
Top View Side View Top View Side View
2. Product Introduction
The AS400 communication card provides contact closures for remote monitoring your UPS. To
meet different application requirement, the AS400 card is capable of selection the status of the
dry-contact signal (active close or active open) by setting jumper. The suitable applications are
listed below:
zIBM Server, Personal PC & Workstations equipments
zAuto-controlled industrial equipment & communication applications
3. Installation
Step 1: Remove cover of Intelligent Slot
on the rear panel of the UPS.
Step 2: Insert AS400 card into Intelligent
Slot.
Step 3: The cover of AS400 should
attach close to the rear panel. Using
screwdriver, secure the AS400 to the
UPS chassis with 2 screws.
Step 4: Use the 9-pin communication cable
to connect UPS and equipment to implement
the remote monitoring and control.
4Specifications .
Internal circuit of DB-9 port
RS-232 port 9-pin port
Electric Parameter of DB-9 port
Symbol
Max.
Min.
Unit
Resistor*
DC Current
IR
6
1
mA
Diode
Reverse Voltage
V R
6
-
V
Forward Current
I F
50
-
mA
Peak Forward Current
I F (Peak)
1
-
A
Relay
DC Voltage
V DC
24
-
V
DC Current
I DC
1.0
-
A
Note: It’s required to retain the DC current lower than 6mA. Otherwise, it’s necessary to add one resistor
within DC current limitation in the serial loop of Remote Shutdown. (e.g. 2K resistor with at least 0.1W
rating power). Refer to diagrams in .Application
Pin Assignment
Pin Assignment
Function
I/O
Pin 1
UPS Failure
O/P
Pin 2
UPS Audible Alarm
O/P
Pin 3
GND (Common for Pin 4)
Power Ground
Pin 4
On/Off
I/P
Pin 5
Common for Relays
Power Supply
Pin 6
Bypass Active
O/P
Pin 7
Low Battery
O/P
Pin 8
UPS On
O/P
Pin 9
Utility Failure
O/P
P.S. The ON/OFF function pin (pin4 & pin3) accepts more than 2s high level signal to perform UPS on and
off actions.
Function Description
AC Status
AO Status
Reason
Pin 1 & Pin 5 connected
Pin 1 & Pin 5 disconnected
UPS failure
Pin 2 & Pin 5 connected
Pin 2 & Pin 5 disconnected
UPS failure, utility failure, low
battery, bypass active
Pin 6 & Pin 5 connected
Pin 6 & Pin 5 disconnected
Bypass active
Pin 7 & Pin 5 connected
Pin 7 & Pin 5 disconnected
Battery voltage is low
Pin 8 & Pin 5 connected
Pin 8 & Pin 5 disconnected
UPS is in inverter mode
Pin 9 & Pin 5 connected
Pin 9 & Pin 5 disconnected
Utility failure
AS-400 Card Remote On/Off Quick Guide V. 3.0
9 pin com. cable

Értékelje ezt az útmutatót

4.6/5 (5 Vélemények)

Termékspecifikációk

Márka: FSP/Fortron
Kategória: nincs kategorizálva
Modell: AS-400

Szüksége van segítségre?

Ha segítségre van szüksége FSP/Fortron AS-400, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek




Útmutatók nincs kategorizálva FSP/Fortron

Fspfortron

Útmutatók nincs kategorizálva

Legújabb útmutatók nincs kategorizálva

Moza

MOZA SR-P Útmutató

10 Április 2025
Caterchef
Ifm

IFM E40581 Útmutató

9 Április 2025
Livn

Livn Bolt Útmutató

9 Április 2025
Livn

Livn Beats Útmutató

9 Április 2025
Ifm

IFM O3R252 Útmutató

9 Április 2025