JK1 Surge Protection Instructions
Instruction leaflet for fitting 125A Surge
Protection
4 pole busbar to be fitted after fitting incomer and phase links (see
incomer instructions).
Please refer to the incomer fitting instructions for fitting of incomer links.
Ensure that all electrical connections on the incomer device are
tightened to 3.5Nm.
Ensure the copper link upper connection points are tightened to 5Nm.
JK101SPD
JK102SPD
Pozidrive
PZ2
2.5mm
8mm
Socket
GB
1ZD0 - Issue 0-18681 89
ZD00868ZD0868
Clip the odule device 4 msurge protection to the
dinrail next to the chosen incomer. (If 3 pole
substitute the neutral connection block with the
KRN199, copper neutral link and M6 carp nut and
tighten the nut to 5Nm.
Mstightened ake ure the phase not links are fitted but
into the incomer terminals.
PKBphaslace the 663E 4 busbar pole into the e
and neutral of the and terminals main switch tighten
the main switch screws. Push the shroud of the
busbar down onto the surge device making sure to
keep it level all and tighten 8 screw terminals to
3.5Nm.
Place the copper earth component into the bottom
two cage terminals and secure to 3.5Nm.
Connect the opposite end to the enclosure using the
2 hex head high-tourqe screws to 3.5Nm.
and fit the shroud provided with the incomer kit by
cutting out the extra modules to accommodate the
surge protection device.
1. 1 x Type I+II or Type II Surge
Protection device
2. 1 x Copper Earth Link
3. 2Hex head Earth screws x
4. 1 x KB663E Busbar (4 pole)
5. 1 x KRN199 Terminal block
6.1 x ZB0220 M6 Carp Nut
7. 1 x Neutral link
Parts list:
The device may only be connected and installed by an electrically skilled person. National standards and safety regulations must be observed.
The device must be checked for external damage prior to installation. If any damage or other defects are detected in this check, the device must not be installed.
Its use is only permitted within the limits shown and stated in the installation instructions.
Opening or otherwise tampering with the device invalidates the warranty.
•Disconnectprotectiveg the plu before conducting insulation
testingonhsystem.therwiseaultyremenare te O f measuts
possible.
•Reinsertthe protectivein plug tothe base element after insu-
lation testing.
Insulation testing

Értékelje ezt az útmutatót

Termékspecifikációk

Márka: Hager
Kategória: nincs kategorizálva
Modell: JK101SPD

Szüksége van segítségre?

Ha segítségre van szüksége Hager JK101SPD, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek




Útmutatók nincs kategorizálva Hager

Hager NCN302A Útmutató

20 Július 2024

Hager BDC280E Útmutató

20 Július 2024

Hager VE106U Útmutató

20 Július 2024

Hager HR831 Útmutató

20 Július 2024

Hager JN212B Útmutató

20 Július 2024

Hager JK104BD Útmutató

21 Július 2024

Népszerű termékek – nincs kategorizálva

Hager TYA610A Útmutató

12 December 2024

Hager 80161869 Útmutató

12 December 2024

Hager VMLF110 Útmutató

17 Szeptember 2024

Útmutatók nincs kategorizálva

Legújabb útmutatók nincs kategorizálva

MOZA SR-P Útmutató

10 Április 2025

IFM E40581 Útmutató

9 Április 2025

Livn Bolt Útmutató

9 Április 2025

Livn Beats Útmutató

9 Április 2025

IFM O3R252 Útmutató

9 Április 2025