Operating instructions
(Safety-related part ATEX / IECEx)
Inductive NAMUR sensors
NS****
80231776 / 00 01 / 2016
UK
2
Remarks for safe use in hazardous areas
Functions and features
Use in hazardous areas according to the classification
II 1G
(group II, category 1G, apparatus for gas atmosphere).
The requirements of the standards EN 60079-0:2009, EN 60079-11:2012,
EN 60079-26:2007+Corr.2009 are met.
II 2G
(group II, category 2G, apparatus for gas atmosphere).
The requirements of the standards EN 60079-0:2009, EN 60079-11:2012 are met.
EC type examination certificate
PTB 02 ATEX 2217
Use in hazardous areas according to the classification
II 1D
(group II, category 1D, apparatus for dust atmosphere).
The requirements of the standards IEC 60079-0:2011, EN 60079-11:2012 are met.
EC type examination certificate
BVS 04 ATEX E153
The requirements of the standards IEC 60079-0:2011+Corr.2012+Corr.2013 and
IEC 60079-11:2011+Corr.2012 are met.
IECEx certificate
IECEx BVS 06.0003
Marking
II 1G Ex ia IIB T6 Ga
II 1D Ex ia IIIC T 90°C Da
II 2G Ex ia IIC T6 Gb
II 1D Ex ia IIIC T 90°C Da
Installation / Set-up
The units must only be installed, connected and set up by qualified staff. The qualified staff
must have knowledge of types of protection, regulations and provisions for apparatus in
hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable
for the application.
Connection only to intrinsically safe certified circuits or evaluation amplifiers which do not
exceed the following maximum values of the units:
Ui = 15 V, Ii = 50 mA, Pi = 120 mW
3
UK
Permissible operating temperature of the application (referred to the maximum permissible
power of 120 mW):
-20...+70°C
Maximum effective internal inductance (Li) and capacitance (Ci):
The values apply to potted cables.
Article no. Cable length Internal inductance
(total) in Hμ
Internal capacitance
(total) in nF
NS5003 2 m 110 80
NS501A 12 m 120 85
Installation remarks / Installation
Adhere to the relevant national regulations and provisions.
Avoid electrostatic charging on plastic units and cables.
Protect the units efficiently against damage.
The cable must be firmly laid and protected efficiently against damage.
The units are not suitable for installation in walls which separate zone 0 from zone 1.
The relevant installation regulations (e.g. EN 60079-14) must be adhered to.
Steps must be taken to ensure the equalisation of potential of metal parts (also fixing
material).
Maintenance / Repair
The unit must not be modified nor can it be repaired. In case of a fault please contact the
manufacturer.
If needed, you can obtain data sheets or EC type test certificates from the manufacturer (see
cover sheet / back).
You can find the IECEx online certificate at www.iecex.com

Termékspecifikációk

Márka: IFM
Kategória: nincs kategorizálva
Modell: NS5003

Szüksége van segítségre?

Ha segítségre van szüksége IFM NS5003, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek




Útmutatók nincs kategorizálva IFM

IFM

IFM E40581 Útmutató

9 Április 2025
IFM

IFM O3R252 Útmutató

9 Április 2025
IFM

IFM PG1704 Útmutató

9 Április 2025
IFM

IFM PE2599 Útmutató

23 Március 2025
IFM

IFM MK5312 Útmutató

23 Március 2025
IFM

IFM RU6035 Útmutató

18 Március 2025
IFM

IFM SF3210 Útmutató

18 Március 2025
IFM

IFM RU6045 Útmutató

18 Március 2025
IFM

IFM KI0200 Útmutató

18 Március 2025
IFM

IFM PT2400 Útmutató

16 Január 2025

Útmutatók nincs kategorizálva

Legújabb útmutatók nincs kategorizálva