–Display of energy consumption for electric
heating systems
–Pulse width modulation (PWM) or two-point
control system
–Adjustable cycle time (PWM), hysteresis and
minimum on/o time (two-point)
–Switch on delay, such as for burners (with two-
point control)
–Adaptation to valves normally open or closed
–Valve protection (as a room temperature
controller with and without a limiting function)
–Resetting separate from user and installer settings
Description of functions
The programmable temperature controller
automatically controls the room or oor temperature
depending on the time and day of the week. The
automated program can be interrupted at any time by
manual entries.
The temperature controller has three selectable
programs for heating which can be adapted to
your individual comfort. The controller is equipped
with an internal sensor for measuring the room
temperature. In addition, an external remote sensor
can be connected, for example to measure the oor
temperature. The temperature controller compares
the measured temperature with set values. If the
temperature falls below the current setting, the
heating system is turned on.
The depends on the type of heating control method
and is determined by the installer:
– The heating is Room temperature controller:
turned on when the room temperature falls below
the set target temperature (measured with an
internal sensor or external remote sensor).
–Floor temperature controller: The oor heating
is turned on when the oor temperature falls
below the set target temperature (measured
using an external remote sensor).
–Room temperature controller with a limiter
(in conjunction with oor heaters):
The room temperature is measured and
regulated using the internal sensor. An additional
external remote sensor is connected to measure
the oor temperature, and a target temperature
range for the oor is set. The room temperature
control is deactivated when the oor temperature
is outside of this range. If temperature falls
below this range, the heater is turned on, and if
the temperature is above this range, the heater
is turned o independent of the current room
temperature.
Operation
(9)
(10)
(11)
(12)
(13)(14)(15)(16)
(8)
Fig. 2: Default display
(8) Function display (such as the mode)
(9) Large display (such as the current temperature)
(10) Day of the week display
(1 = Monday ... 7 = Sunday)
(11) Heating mode display
(12) Display (such as the current time)
(13) O button (info/OK)
(14) + button
(15) - button
(16) M button (menu)
Safety instructions
The unit may only be opened by an electrician
and installed according to the circuit diagram on
the unit or in these instructions. Observe existing
safety instructions.
To satisfy the requirements of protection class
II, corresponding installation measures are
required.
This independently installable electronic device
is exclusively for controlling the temperature in
dry, enclosed rooms with normal surroundings.
This device is in conformance with EN 60730 and
functions according to operating mode 1C.
Damage to the device, re or other hazards may
arise if these instructions are not followed.
These instructions are a component part of the
product and must remain with the end customer.
Structure of the device
(2)
(3)
(1)
(4)
(5)
(6)
(7)
Fig. 1: Layout of the temperature controller
(1) Controls
(2) Display
(3) Control buttons
(4) Plug-in contacts
(5) Design frame (not including delivery)
(6) Socket for the plug-in contacts
(7) Use
Function
Correct use
–Measuring and controlling the room temperature
–Measuring and controlling the oor temperature
–Room temperature control via oor heating with
a limiting function (for example in conjunction
with tiled stoves)
–Can be used for “heating only” or “cooling only”
–Installable in a box in conformance with
DIN 49073
–Only for use in dry, enclosed rooms
Product characteristics
–Large display with backlighting
–Text display for self-explanatory operation
–Programmable even when the controls are
removed
–Dierent user languages can be selected
–Real-time clock with automatic switchover to/
from daylight savings time
–Internal temperature sensor
–An external remote sensor can be connected
–Three selectable and adjustable time
temperature programs for automatic mode
–A maximum of nine operating times per day (the
setting can also be terminated after a specic
operating time)
–Can be individually programmed every day, or a
block of operating times can be set: workdays/
non-workdays, all days the same
–Can be manually adjusted at any time
–“Vacation” mode with the entered date (from/to)
–“At-home” mode (present)
–Short-time timer (“party function”)
–Optimum start” function (the temperature is
reached at the set time)
–Protection against frost
Universal room temperature controller
with display
Ref.-no.: TR UD .. 231 ..
Operating instructions
GB
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Tel. +49 2355 806-0
Fax +49 2355 806-204
kundencenter@jung.de
www.jung.de
08/2015
0024073501
Termékspecifikációk
| Márka: | Jung |
| Kategória: | Termosztát |
| Modell: | TRUDA231 |
Szüksége van segítségre?
Ha segítségre van szüksége Jung TRUDA231, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók Termosztát Jung
Jung TRUDES231 Útmutató Jung AHLK-FT Útmutató Jung TRDLS231 Útmutató Jung CD2178TS KNX Útmutató Jung TRAL241 Útmutató Jung CDHLK-FT Útmutató Jung AUT238D Útmutató Jung TRUDME231 Útmutató
Összes Jung Termosztát használati útmutató
Népszerű termékek – Termosztát
Útmutatók Termosztát
Legújabb útmutatók Termosztát
Fantini Cosmi L03B Útmutató Fantini Cosmi L02A Útmutató Fantini Cosmi L02C Útmutató Fantini Cosmi C820RQ Útmutató Fantini Cosmi C800WIFI Útmutató Wodtke FT1 Útmutató Emmeti CS-11 - U9310047 Útmutató Worcester-Bosch Greenstar Comfort I RF - 2023 Útmutató Fantini Cosmi L02D Útmutató Etherma eTOUCH mini Útmutató