Use appropriate personal protective equipment
such as safety glasses, face shields, insulating
gloves, insulating boots, and/or insulating
mats.
Use the 3-Step Testing Method. Before each
use:
Verify tester operation by measuring a
known voltage. Apply tester to circuit under
test. And, then test on the known live volt-
age again to ensure proper operation.
Connect the black common lead to ground
before applying the red test lead to voltage.
Disconnect the red test lead from the volt-
age first.
Always work with a partner.
When using the probes, keep fingers as far
behind the probe tips as possible.
Features:
Vibration Mode with indicator movement
Independent solenoid and electronic circuitry
design provides back-up voltage indication
for added safety
Low Impedance Measuring Device
Replaceable Test Leads
Shielded probe tips
Ultrasonically welded for added durability
Accessories:
61-072 Resistor-fused test leads
C-90 Soft-sided carrying case
61-010 Leather case
To Measure AC Voltage:
Ensure that the plug for the test leads is fully
seated into the banana jacks.
Connect the tester in parallel with the load or
circuit.
The tester indicates both the voltage type and
the voltage level.
To Measure DC Voltage:
Ensure that the plug for the test leads is fully
seated into the banana jacks.
Connect the tester in parallel with the load or
circuit.
The tester indicates the voltage type, polarity,
and the voltage level.
2
Voltage Tester
Instruction Manual
WARNING
Read First: Safety Information
Use the tester only as specified in this manual;
otherwise, the protection provided by the tester
may be impaired.
Warning
To avoid possible electric shock or personal
injury, follow these guidelines:
Do not use tester if it is damaged. Visually
inspect tester to ensure case is not cracked.
Inspect and replace leads if insulation is
damaged, metal is exposed, or probes are
cracked. Pay particular attention to the
insulation surrounding the connectors.
Do not use tester if it operates abnormally as
protection maybe impaired.
Do not use during electrical storms or in wet
weather.
Do not use around explosive gas, dust, or vapor.
Do not apply more than the rated voltage to
the tester. Voltage is not to exceed 600V.
Always operate this solenoid-type tester
within the specified duty cycle on the front of
the tester. Duty cycle ratio is:
1:7 ON:OFF time for 240V or less
1:40 ON:OFF time for 240V or greater.
Maximum ON time is 15 seconds.
Caution
To protect yourself, think "Safety First":
Voltages exceeding 30VAC or 60VDC pose
a shock hazard so use caution.
Never ground yourself when taking electrical
measurements.
#61-065