NetBotz® Spot Fluid Sensor (NBES0301)
Installation Instructions
The NetBotz Spot Fluid Sensor enables you to monitor a remote location for the presence of any
liquid with a resistivity of less than 2 MOhms per cm (including distilled water).
Note: You can extend the length of the cable up to 30.5 m (100 ft) using the RJ-45
coupling and standard CAT-5 cabling.
Installation
1. Place the fluid-sensing portion of the NetBotz Spot Fluid Sensor at the location that you want
to monitor. The four fluid sensor contacts should be in direct contact with the surface.
2. Plug the cable into an available Sensor Port on your NetBotz appliance
Spot Fluid Sensor
Plastic insulation sheet
203-mm (8-in) tie wraps (10) Adhesive cable tie holders (5)
RJ-45 coupling (1)

Customer support and warranty is available at the APC Web site information , www.apc.com.
© 2013 Schneider Electric. APC, the APC logo, InfraStruxure, and NetBotz are owned by Schneider Electric
Industries S.A.S.or their affiliated companies. All other trademarks are property of their respective owners.
990-3294A
0 /203 13
Using the Insulator Sheet on a Conductive
Surface
The NetBotz Spot Fluid Sensor uses electronic
circuits to detect the presence of fluid. If the sensor
contacts are shorted, the uid detection circuits
will not work. Shorting can occur when the sensor
is placed on a metal surface, or on some materials,
such as cement ooring (particularly cement that is
wet), that may be conductive and grounded.
Place the Spot Fluid Sensor on the provided insulator sheet to avoid shorting the contacts.
Configuring the Spot Fluid Sensor
Once the Spot Fluid Sensor is conected to the NetBotz Appliance, it will be detected automatically,
and will appear in the Sensor Readings pane.
The Spot Fluid Sensor is a normally open (NO) dry contact sensor. Use the Dry Contact task to
configure the settings for the NetBotz Spot Fluid Sensor. See the NetBotz Appliance User’s Guide
for more information about the Advanced View.
Caring For and Cleaning Your Sensor
While your Spot Fluid Sensor is fluid-resistant, it is intended for leak detection only and is not
designed to be immersed for extended periods of time. Use only plain tap water to clean your Spot
Fluid Sensor. Do not use soap or detergents of any kind. In addition, the RJ-45 coupling should not
be an area where water will collect or condensation may form, as this may corrode the coupling.
Termékspecifikációk
Márka: | APC |
Kategória: | nincs kategorizálva |
Modell: | NetBotz NBES0301 |
Szüksége van segítségre?
Ha segítségre van szüksége APC NetBotz NBES0301, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók nincs kategorizálva APC
9 Április 2025
29 Március 2025
29 Március 2025
29 Március 2025
11 December 2024
11 December 2024
5 December 2024
15 Október 2024
14 Október 2024
4 Október 2024
Útmutatók nincs kategorizálva
- nincs kategorizálva Tsakalis AudioWorks
- nincs kategorizálva Imperia
- nincs kategorizálva Hanwha
- nincs kategorizálva Christmaxx
- nincs kategorizálva XGIMI
- nincs kategorizálva Herma
- nincs kategorizálva Piko
- nincs kategorizálva ELMEKO
- nincs kategorizálva Comtek
- nincs kategorizálva System Sensor
- nincs kategorizálva WeFix
- nincs kategorizálva Datacard
- nincs kategorizálva Wireless Solution
- nincs kategorizálva ESYLUX
- nincs kategorizálva VAX
Legújabb útmutatók nincs kategorizálva
10 Április 2025
10 Április 2025
10 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025
9 Április 2025