1.Introduction
1.1 Key Characteristics
1.2 Pulse output
1.3 RS485 Serial – Modbus RTU
1.4 Mbus for SDM230-Mbus
User Manual V1.6
SDM230 Series
Single Phase Two Wire Multifunction Din Rail Meter
.
T h e b i- di re c t i o n al m ea su re me nt m ak e s t h e m e t e r
s u i t a bl e f o r a ct iv e a n d r e ac t iv e e n e r gy a n d p o w er
mon itor ing app licatio ns, and al so pe rf ec t f or s ol ar PV
me as ur emen ts . Wit h RS 48 5 M od bu s an d M -b us p or t,
the me ter is eas y to remo te co mmun ic at io n wit h ot he r
AMR/SCADA systems.
·Bi-directional measure and display
·Multi-function measurements
·Two Pulse outputs
·RS485 Modbus / M-bus
·100A direct connection
·Two module size (35mm)
·Password protected set-up
·Backlighted LCD
·2 tariff dual power source
The meter provides two pulse outputs. Both pulse outputs
are passive type.
Pulse output 1 can be set to generate pulses to represent
total / import/export kWh or kVArh.
The pulse constant can be set to generate 1 pulse per:
0.001/0.01/0.1/1kWh/kVArh (default is 0.001 export kWh).
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed up with active
kWh (Imp). The constant is 1000imp/kWh.
RS485 serial port with Modbus RTU protoco l to provide
a me ans o f r em ot el y m on ito ri ng a nd c on t r oll ing t h e
Uni t . Se t- up s cr e e ns a re p ro vi d e d f o r se t ti ng up th e
RS485 port.
This unit has an M-BUS serial port with M-BUS protocol
to provide a means of remotely monitoring and controlling
the unit set-up screens are p rovi ded for se tti ng up the
M-bus port.
1.5 2T by time relay for SDM230-2T
The unit has a time relay inside which can monitor if there
is external 230V signal input. If there is 230V signal inp ut,
the meter switches Tariff 2 measurement, otherwise it will
measure as Tariff 1.
2.Operation
2.1 LCD Display
Model Measurements Pulse Outputs Multi
Tariffs
SDM230-
Modbus
U, I, P, Q, S , PF, Hz,
Dmd, kWh, kVArh,
Import, Export
RS485
Modbus
1:
congurable
2:
1000imp/kwh
NO
SDM230-
2T
1:
congurable
2:
1000imp/kwh
U, I, P, Q, S , PF, Hz,
Dmd, kWh, kVArh,
Import, Export
SDM230-
Mbus
U, I, P, Q, S , PF, Hz,
Dmd, kWh, kVArh,
Import, Export
M-bus
EN13757-3
1:
congurable
2:
1000imp/kwh
NO
Communi-
cation
1
1
1
11
2
2
2
22 3
3
3
33 4
4
4
44 5
5
5
55 6
6
6
66
7
7
7
77
8
8
8
88
9
9
9
99
1
1
1
110
0
0
00
11
11
11
1111
1
1
1
112
2
2
22
1
1
1
113
3
3
33
2 Tariffs
(time relay)
RS485
Modbus
10 Import(input)reactive energy
Example: 5.00kVArh
11 Export(output)reactive energy
Example: 5.00kVArh
9
T2 reactive energy
Example: 2.00kVArh
(for SDM230-2T only)
The setting is done correctly
The entering information is
wrong. The operation fails.
12 Resettable total energy
Warnings
Im p or ta nt S af e ty In fo rma ti o n i s con t ai n ed in th e
Maint enance sect ion. Famili arize yourself with this
infor mation befo re attempti ng ins tal lat io n or o the r
proce d ures.
Risk of Danger: These instructions contain
important safety information. Read them before
starting installation or servicing of the equipment.
Caution: Risk of Electric Shock
!
!
!
!!
11
NO.
2
3
4
5
6
7
8
9
10
13
Descriptions
7 digits used to display measured values
Total value
Import information, Export information
Max. Demand for Power or Current.
Pulse output 1and Pulse output2
Measurement units
PF = power factor Hz = frequency
Bar display of Power
Communication indicatior
Lock symbol
Tariff information
2.3 Scroll display by Buttons
After initialization and self-checking program, the meter
display the measured values. The default page is total
kWh . If the user wa nts to ch eck oth er inf orma tion , he
needs to press the scroll button on the front panel.
The display order by scroll button :
Total kWh→ Import kWhExport kWh→ Resettable kWh
Total kVArhImport kVArh→ Export kVArh→Resettable kVArh
→ Max. Power Demand→ VoltageCurrentWVar →
VA→ Power FactorFrequency →Pulse Constant→ Modbus ID
Baud Rate →Continuous Running Time
Display No:1,4~7,10~24.
*For SDM230-Modbus:
*For SDM230-2T:
Total kWh→ T1 total kWh→ T2 total kWhImport kWh→
Export kWh →resettable kWh→Total kVArhT1 total kVArh
→T2 total kVArh→Import kVArh→ Export kVArh→ resettable kVArh
Max. Power Demand→ Voltage CurrentW→ Var →VA
Power Factor Frequency Pulse Constant Modbus ID
Baud Rate Continuous Running Time
Display No: 1~24.
7Total reactive energy
Example: 10.00kVArh
Software version (please check
the real software version on the
product as the final).
Modbus ID or Mbus Primary Address
2.2 Initialization Display
All dis play s egments light up,
display check.
*For SDM230-Mbus:
Total kWh Impor t kWh Expo rt kWh Resettable kWh
Total kVArh Import kVArh Export kVArh→ Resettable kVArh
Max. Power Demand Voltage CurrentW→ Var →VA
→ Power Factor → Frequency →Pulse Constant
Mbus Primary AddressMbus Secondary Address
Baud Rate→Continuous Running Time
Display No:1,4~7,10~24.
2
T1 active energy
Example: 10.00kWh
(for SDM230-2T only)
3
T2 active energy
Example: 10.00kWh
(for SDM230-2T only)
1Total active energy
Example:70.00kWh
4Import(input) active energy
Example: 50.00kWh
5Export(output) active energy
Example: 20.00kWh
8
T1 reactive energy
Example: 2.00kVArh
(for SDM230-2T only)
6Resettable total energy
2.4 Set-up Mode
To get into Set-up Mode, the user needs to press the “Enter
button for 3 seconds.
17 Reactive power
Example: 1030Var
18 Apparent power
Example: 4811VA
19 Power factor
Example: 1.000
20 Frequency
Example: 49.99Hz
21 Pulse 2 constant
Example: 1000
22
Modbus address
Example: 001
Mbus primary address
Example:001
22-1
High and Low bit of MBUS
Secondary address
(Default 00 00 00 01)
Example: if the Secondary
address high bit is 0000,
low bit is 0001,that means
the integral Secondary
address is 00 00 00 01
(for SDM230-Mbus only)
23 Baud rate
Example: 9600
Continuous running time
(since last time reset)
24
This document provides operating, maintenance and
installation instructions of SDM230 series made by
Ea str on E le ct ron ic Co . , L td . Th e S DM 23 0 s er ies
measure and display the characteristics of single phase
two wire (1p2w) network. The SDM230 series covers 5
m o de l s : S DM 2 3 0 - M od b u s , SD M 2 3 0 -P u l s e , SD M 2 3 0 -
Mbus, SDM230-2T and SDM230-Std.
SDM230-
Pulse
U, I, P, Q, S , PF, Hz,
Dmd, kWh, kVArh,
Import, Export
NO
1:
congurable
2:
1000imp/kwh
NO
SDM230-
Std
1:
congurable
2:
1000imp/kwh
kWh, kVArh,
Import, Export
RS485
Modbus NO
Baud rate.
Total kWh.
Mbus Secondary Addres s (Low)
(for SDM230-Mbus only)
Mbus Secondary Addres s (High)
(for SDM230-Mbus only)
Total kWh→ Import kWhExport kWh→ Resettable kWh
total kVArhImport kVArh→ Export kVArh→resettable kVArh
→ Max. Power Demand→ VoltageCurrentWVar →
VA→ Power FactorFrequency →Pulse Constant
Display No:1,4~7,10~21.
*For SDM230-Pulse:
*For SDM230-Std:
Total kWh Impor t kWh Expo rt kWh Resettable kWh
Total kVArh Import kVArh Export kVArh→ Resettable kVArh
Pulse Constant→ Modbus ID→ Baud Rate →
Continuous Running Time
Display No:1,4~7,10~12, 21~24.
16 Active power
Example: 4700W
Current
Example: 30.156A
15
Voltage
Example: 229.8V
14
13 Max. power demand
Example: 6938W