The ATS-10providesthemainsvoltagemonitoringandautomatictransferswitching.Intheeventofamains
voltagefailure,theremotestartrelayoutputisenergizedandtheunitautomaticallytransferstheloadfromthe
mainstothegenerator.Microprocessortechnologyallowsexactmeasurement,setpointadjustmentandtiming
functionswiththeparameterstobesimplyprogrammedanddisplayedfromthefrontpanel.
The ATS-10automatictransferswitchcandetectfailureofanyphaseofthemainssupply.Ifatleastoneofthe
mainsphasevoltagesgoesoutsidesetlimits,theunitoperatesasfollows:
- Theledturnsfromgreentored. Themainscontactoroutputisdeenergizedandthe
green ledisextinguished.
-TheremotestartoutputisenergisedaftertheRemoteStartDelayparameterhasexpired. Thegenerator
startmodulereceivesthissignalandinitiatestheenginestart.
-IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1);Whenthegeneratorvoltageiswithinset
limits,theyellowledwillilluminate. Theunitwillallowthegeneratingsettorunwithout
loaduntiltheEngineHeatingPeriodparameterisexpired. Afterthistime,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
IftheUnitUsage Typeparameter(P00)isselectedas1(Type-2);WhentheEnginerunningsignalis
present,theyellowledwillilluminate. Theunitwillallowthegeneratingsettorun
withoutloaduntiltheLoadgen.signalispresent.Ifthissignalispresent,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
- Thegeneratorcontactoroutputwillbeenergizedandtheyellowledwill
illuminatesteadilywhentheGeneratorContactorDelayparameterisexpired.
-Ifthemainsvoltagereturntowithinlimits,the ledwillturntogreenandtheunitwaits
fortheMainsReturndelayparameterforthemainsvoltagestabilization.
-WhentheMainsReturnDelayparameterisexpired,theyellow ledis
extinguishedandthegeneratorcontactoroutputisdeenergized. Thenthegreen
ledwillstartblinkingandthentheunitwillwaitfortheMainscontactorDelayparameter.
-WhentheMainscontactorDelayparameterisexpired,thegreen ledwill
illuminatesteadilyandthemainscontactoroutputisenergized. Thentheremotestartoutputisdeenergized.
- Theunitisreadyforanewmainsfailure.
The ATS-10hasgotaTEST modefeature.Thismodeallowsthegeneratingsettobetestedwithouttakingthe
load. ThismodeisalsocalledEmergencybackupmodewhichkeepsthegeneratingsetrunningandmakesa
quicktransferifamainsfailureoccurs.
Inthismode, Theremotestartoutputwillbeenergizedbutnoloadtransferwilltakeplaceunlesstheoccurrenceof
amainsfailure.Ifamainsfailureoccurs,theloadwillbetransferredtothegeneratingset.Ifthemainsvoltage
returntowithinlimitsandtheMainsReturnDelayparameterisexpired,theloadwillbetransferredtothemains,
butthegeneratingsetwillbekeptrunning.Theremotestartoutputwillonlydeenergizedwhenthe Testmodeis
cancelled.
MainsVoltageOkay
MainsContactorClosed
GeneratorRunning
GeneratorContactor
Closed
GeneratorRunning
GeneratorContactor
Closed
GeneratorContactorClosed
MainsVoltageOkay
GeneratorContactorClosed
MainsContactorClosed
MainsContactorClosed
1
Automatic Transfer Switch, 72x72DIN Size
ATS-10
Automatic Transfer Switch
72 x 72 DIN Size
IntroductionBrochure.ENG ATS-1001V0207/16
Termékspecifikációk
| Márka: | Emko |
| Kategória: | nincs kategorizálva |
| Modell: | ATS-10 |
Szüksége van segítségre?
Ha segítségre van szüksége Emko ATS-10, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók nincs kategorizálva Emko
Emko Trans-MidiAMF Útmutató Emko IPERTU Supply Útmutató Emko proop7L Útmutató Emko EZM-9920 Útmutató Emko ESM-3712-H Útmutató Emko EPM-3790 Útmutató Emko EPM-7790 Útmutató Emko EAOM-11.2 Útmutató