V3IS00462-010
CH4 SensorCO SensorLPG Sensor, and areprobesforthedetectionof
methanegas,carbonmonoxideandLPGtobeconnectedtoSRG and SRG.4
controlunitstocreatesystemsfordetectinggasinareassuchasboilerrooms,
warehouses,etc.
It is wall-mounted in a vertical position using screws and plastic plugs.
SAFETY WARNINGS
During installation and operation of the instrument, comply with the
following instructions:
1) The device must be installed by a competent person
2) Before removing the cover, make sure that power is NOT provided to
the device
3) Before accessing the terminals, make sure that the electrical leads are
not live
4) Install the detector in the correct position (see “Installation”)
5) Do not power on the device if any part of it is damaged
Code Model Description
VE205100CH4SENSOR Methanedetectionsensor
VE206900 LPG SENSOR LPG sensor
VE207700 CO SENSORCarbonmonoxidesensor
TECHNICAL CHARACTERISTICS
• Powersupply:fromthecontrolunitSRGorSRG.4
 −Currentinput(at6.5V):40mA
 −Connection:terminalsof2.5mm2C(common),S(signal),A(powersupply)
• Modelsandcalibration:
 −Methanegas:CH4Sensor,(default)10%LIEofmethane
 −LPG:LPGSensor,(default)12%LIEofisobutene
 −Carbonmonoxide:COSensor,(default)200ppmofcarbonmonoxide
• Max.lengthofconnection:50m
• Container:inself-extinguishingplasticmaterial
• Fastenedtowallusingscrewsandplasticplugs
• Protection:IP30
• Operatingtemperature:0÷+50°C
•Humidity: 90%R.H.withoutcondensation≤
INSTALLATION
 LPG,COandCH4Sensorsaredesignedtobewall-mounted(vertically),using
screwsandplasticplugs.Toproceedwithinstallation,openthecontainerby
unscrewingthescrewlocatedonthelowerside.Makesurenottodamagethe
sensorandnottotouchthecalibrationdevices.
POSITIONING
 Thecorrectinstallationoftheprobeisessentialtoproperoperationofthe
system.Therefore,itmustbeinstalled:
• Inareaswithcirculationofnaturalair;
• Inareasthatarenotsubjecttodustordirtthatmayrenderthesensor
inoperative;
• Nearjetsofwater,intakegrilles,openings,etc.
• Atanadequatedistancefromusersofgassoastopreventthesystemfrom
interveningimproperlyduetofunctionalleakage.
 Also,positioningdependsonthetypeofgastobedetected,specically:
• CH4 Sensor: Methane gas – at top, about 20-30 cm from the ceiling
• LPG Sensor: LPG – at bottom, about 20-30 cm from the floor
• CO Sensor: carbon monoxide – about 1.5 m from the floor
 Fornewsystems,theprobemustbeinstalledaslateaspossible,sothattypical
constructionsiteactivitiesdonotdamagethedetector.
CONNECTIONS
 Normalelectricalcablescanbeusedforconnections.Inanycase,when
installationisinplacesthatarestronglyexposedtoelectromagnetic
disturbances,itisadvisabletouseshieldedcables.Thedetectionsystemmust
alwaysbeinoperation.Therefore,theelectricalpowersupplyofthedetector
mustnotincludeswitchesorotherdevicesthatmayaccidentallyshutitoff.The
averagelifespanoftheprobesis5yearsfromthedateofinstallation.Therefore,
attheendofthattimetheywillneedtobereplaced.
Note. Make sure you check operation at least once a year, and in any
case whenever there is an extended period of disuse or in the event of
replacement. Any tampering may compromise correct operation of the
system.
REFERENCE STANDARDS
CompliancewithCommunityDirectives:
2006/95/EC (lowvoltage)
89/336/EECmod.from andfrom92/31/EEC 93/68/EEC(E.M.C.)
isdeclaredwithreferencetothefollowingstandards:
EN 61779-4, EN 50270
User Manual
SENSORS FOR SRG/SRG.4 CONTROL UNITS
Read all the instructions carefully
Dimensions
Connection diagrams
119,0
75,3
75,3
36,0
CH4 SENSOR
C SA
C SA
SRG/SRG.4
Mod. CH4 SENSOR
Mod. LPG SENSOR
Mod. CO SENSOR