USER GUIDE GB
RF basic thermostat WFHTRF 010 (20433)
TECHNICAL CHARACTERISTICS
MODES DESCRIPTION
- Radio frequency RF thermostat (433.92 Mhz) specially designed for water floor
heating. (Personal code on each product)
- Equipped with a LCD display to select comfort ( ), Off or night reduction ( )
mode.
- Setting and room temperature displayed.
- To be used only with ours receivers.
PPL IMP 1017A
Measured temperature precision 0.1°C (or 0.2°F)
Operating temperature 0°C - 50°C (or 32°F – 122°F)
Setting temperature range 5°C - 37°C by 0.5°C step (or 41°F - 99°F by 0.5°F step)
Regulation characteristics
Proportional Integral regulation (adjustable see installation
menu) Cycle: 15 minutes or Static differential 0.3°K
Anti-short cycle: 3min in OFF, 2min in ON.
Electrical Protection Class II - IP30
Power Supply
Battery operated life
2 x 3V (CR2430)
~ 2 years
Radio frequency 433.92 MHz, <10mW.
certifications CE. EN 300220-1, EN 301489-1
(Radio frequency certifications)
Soft version Displayed when the thermostat is turn Off
RADIO CONFIGURATION MODE
• To assign (*) the RF thermostat with the receiver you must put the receiver in
“RF init” mode (please refer to the receiver leaflet).
• After you have just Press key during 5 sec, when the display( rF “”)
• The thermostat sends its configuration address by radio signal.
• When the receiver is configured, Press key to return to user menu.
* (In this mode the thermostat should be near the receiver)
COMFORT operating mode:
Force comfort temperature operation indefinitely.
By pressing
&
keys the comfort temperature starts to blink and can be adjusted.
The measured temperature reappears after a few seconds.
OFF mode:
Use this mode if your Heating installation needs to be turned OFF.
The display is blank.
(Careful in this mode your installation can freeze)
Parameters are saved.
REDUCED operating mode:
Force reduced temperature operation indefinitely.
By pressing
&
keys the comfort temperature starts to blink and can be adjusted.
The measured temperature reappears after a few seconds.
1: Operating mode menu
2: Heater indication
3: Cooler indication
4: Batteries weak
5: If lit-up 6 displays the measured temperature
6: Measured temperature or set temperature
7: Moving bars when transmitting a radio signal
Or Title for installation Parameters (rF, J0,CLr…)
DISPLA
Y
Press the key during 5 seconds, Then use or keys to select the installation parameter to be adjusted.
Press to toggle the parameter setting or edit the value. If the value starts to blink you can use
&
keys to
adjust this value. Press & keys at the same time to reset this value to the factory default value. Once you have
adjusted the value press to validate this parameter value. When you have finished, use &
keys to go to
‘rF’ display and then press key to exit installation parameter menu.
rF : Radio configuration mode (see section). Press to return to normal operation modes.
J0 : °C / °F temperature display selection
J1 : “Hot” / “Cold” regulation mode. Select Hot for a Heater system, select Cold for a Cooling system
Cy : Proportional Integral regulation time cycle value in minutes (default: 15 minutes cycle)
bp : Proportional Integral regulation band amplitude value in degrees °C/°F (default: 2.0°C/3.6°F)
J5 : Select “PMP” to perform an 1 minute exercise everyday (if installation inactive during a day)
J6 : Air or Floor temperature regulation selection. (if no Floor sensor, regulation will use Air sensor)
J7 : “rEG” (Proportional Integral) or “HYs” (0.3°K Hysteresis) regulation type selection
Cp : compensation value in °C/°F (default: 2.0°C/3.6°F) this parameter must be adjusted by a professional.
Ao : Air sensor offset adjustment (default: no offset). Display measured Air sensor value
Fo : Floor sensor offset adjustment (default: no offset). Display measured Floor sensor value
FL : Floor temperature LOW limitation (default: 5°C/41°F), effective only if floor sensor present
FH : Floor temperature HIGH limitation (default: 28°C/82°F) , effective only if floor sensor present
CLr : Press key during 5s to reset all the WFHT LCD parameters to factory defaults
* (Default parameters are underlined.)
INSTALLATION PARAMETERS MENUS
Optional external sensor 10K
Termékspecifikációk
| Márka: | Watts |
| Kategória: | Termosztát |
| Modell: | WFHTRF 010 -20433 |
Szüksége van segítségre?
Ha segítségre van szüksége Watts WFHTRF 010 -20433, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók Termosztát Watts
22 Március 2025
20 Március 2025
12 Augusztus 2024
3 Augusztus 2024
31 Július 2024
30 Július 2024
21 Július 2024
20 Július 2024
15 Július 2024
Útmutatók Termosztát
- Termosztát Helios (Amfra)
- Termosztát Webasto
- Termosztát De Dietrich
- Termosztát Gira
- Termosztát Crestron
- Termosztát HomePilot
- Termosztát Braeburn
- Termosztát Heimeier
- Termosztát PECO
- Termosztát Saunier Duval
- Termosztát Econo-Heat
- Termosztát IR-V
- Termosztát Perel
- Termosztát AWB
- Termosztát Jung
Legújabb útmutatók Termosztát
9 Április 2025
7 Április 2025
7 Április 2025
6 Április 2025
6 Április 2025
6 Április 2025
5 Április 2025
4 Április 2025
4 Április 2025
3 Április 2025